News Category

What are the requirements for self-ballasted lamp load control cabinets in the IEC 60669-1 standard?

Views : 37
Author : Zhang
Update time : 2023-10-16 11:10:28
What are the requirements for self-ballasted lamp load control cabinets in the IEC 60669-1 standard?
 
According to IEC 60669-1-2017, clause 19.3, switches used for the control of self-ballasted lamps shall withstand the electrical and thermal stresses that occur when controlling self-ballasted lamp circuits without undue damage or other detrimental effects.
 
The expected short-circuit current (r. m s.) of the power supply for testing shall be between 3 kA and 4 kA at cos$=0.9±0.05 (hysteresis) F shall be a copper wire fuse having a nominal diameter of 0.1 mm and a length of not less than 50 mm R1 shall be a resistor limiting the current to approximately 100 A. The switch shall have an appropriate length of two-core cable. The double-core cable shall be of such length that the resistance of the test circuit to the load, R3, is equal to 0.25 Ω. When the rated current of the switch under test does not exceed 13 A, the cross-sectional area of the double-core cable is 1.5 m m²: when the rated current of the switch under test exceeds 13 A, but does not exceed 20 A, the cross-sectional area of the double-core cable is 2.5 m m. The test load shall be of the same type as that shown in Fig. 14, with a copper fuse of nominal diameter 0.1 mm and length of not less than 50 mm.
 
The load for testing shall be consistent with Figure 14b (see Appendix C). The maximum peak current and maximum inrush current I2t values are given in Table 19.
 
Note 1: R2 for the total series resistance of the light circuit, including the ESR (equivalent series resistance) value of the capacitor.
 
SH6331 intelligent self-ballasted lamp power load control cabinet according to IEC 60669-1 in Chapter 19.3 of the self-ballasted lamp load test requirements. Ballast lamp load test requirements for design and manufacture. This load cabinet simulates the use of LED and other lamps and lanterns in a charged state, and can provide various types of electrical accessories with rated currents, peak inrush currents and Power factor greater than 0.85 test load.
The equipment adopts professional design overall appearance is generous and beautiful, durable. Casters are installed under the box, which is convenient to move. The equipment adopts high-grade PLC control, the display interface is 7-inch touch screen, the equipment operation is stable, convenient and practical. Stable operation, convenient and practical. In order to facilitate customers to adjust the parameters, the equipment according to common standard parameters, built-in nearly 30 kinds of commonly used parameter modes, can quickly and easily adjust the current, power factor and other parameters, even if the first operation is not skilled, can also be used to adjust the current, power factor and other parameters. Even if you are not skilled in the first time operation, you can accurately and quickly adjust to the required parameters. In addition, the device is reserved for customised modes (including ordinary load and fluorescent lamp special mode), which can be adjusted and saved according to the actual needs. In addition, the device is reserved for customised modes (including normal load and special mode for fluorescent lamps), which can be adjusted and saved according to the actual needs, and then quickly adjusted to the required parameters when used again.
 
  Technical performance and parameters
1. Control input power: AC220V/50Hz/6A.
2. Load type: LED lights or similar load on and off test.
3. voltage range: 100 ~ 275V continuous automatic adjustment (with the load must ensure that the load input power supply for AC220V 240V).
4. Rated current output range: 0~20A can be set.
5. Current peak value, waveform integral area corresponding to the rated voltage and rated current are shown in the following table.
 
6. control system: PLC.
7. Display: 7 inch touch screen.
8. Setting data with power-down protection function.
9. Load output: 2 ways
10. Voltage, current peak, waveform area deviation 5%.
11. current deviation 5%; cos in deviation of 0.02.
12. the ratio of on-off time: through 30%, 70% disconnected. Internal restrictions shall not be greater than 50%: 50%.
13. Independent fan forced cooling